Case Study: Underground 600mm Concrete Water Main Pipe Break Repair in Canada
A city authority in Canada repair a difficult break in an underground 600mm diameter concrete water main pipe at the point the line passed through a wall. The application reduced a leak losing significant amounts of water when the pipe was fully pressurised at 2 bar down to a slow and steady drip.
Case Study Overview
Site Public Water Network
Location British Columbia, Canada
Repair Type Leak repair
Defect Crack in a 600mm diameter concrete water supply pipe
Repair Products
Sylmasta AB Original Epoxy Putty,
SylWrap Pipe Repair Bandage
Case Study PDF
Case Study Details
The 600mm diameter pipe ran beneath a road in a city in British Columbia. A break was detected and with other concrete pipe bursts making headline news across Canada, the city authority carried out an immediate excavation to assess the problem and repair the leak.
A steady, hard spray of water was discovered jetting out of the pipe through a joint at the exact point the line passed into a solid concrete wall. This made identifying the exact source of the leak impossible.
The city authority contacted Sylmasta for help with what was a very challenging application. Not only was the precise leak point unknown, but the pipe was unable to be fully shutdown.
A further complication came with the break being so close to the wall, meaning the normal live leak repair method of applying Wrap & Seal Pipe Burst Tape would be ineffective.
There was insufficient space to stretch the tape by the required 300 percent to ensure it successfully amalgamated to form a solid rubber band.
Sylmasta suggested reducing the pressure as much as possible from the 2 bar the pipe operated at, followed by using AB Original Epoxy Putty to seal around the entire joint.
AB Original was recommended because it has excellent underwater adhesion, meaning it could bond to the pipe even if wet from the ongoing leak. Its two-hour work time also offers longer to work the putty without worrying about premature curing during application.
The importance of the pipe to the city network meant pressure could only be reduced between midnight and 5am, giving the two maintenance workers making the repair a five-hour window in which to work.
Just under 8kg of AB Original was used in the repair, supplied in 200g sticks. Each stick was mixed by hand until it turned a uniform colour. It was then packed around the leaking joint, building a repair which encompassed the entire break area.
Despite water pouring out the top of the pipe during the repair, AB Original bonded successfully. After two hours, the putty had set to form a watertight material which reduced the amount of water being lost down to a slow drip.
The pipe was then wrapped with SylWrap Pipe Repair Bandage for added reinforcement. Two SYL866HD were used, creating a rock-hard outer shell to further protect the pipe and help increase the effectiveness of the repair.
Completing the application took around three hours. The city authority were particularly impressed with Symasta’s efficiency. It took under five days from initial contact for a repair method to be devised, the goods shipped from the UK to British Columbia and the leak reduced to an acceptable level until the section of pipe can be replaced.
The need for speed in addressing the leak before it could escalate into a major problem was particularly important at a time when Canada’s pipe network is under scrutiny following high-profile bursts in Calgary and Montreal which led to flooding and the rationing of public water supplies.
Products Used
AB Original Epoxy Putty Stick
Epoxy putty with high wet surface adhesion and an extended two-hour work time
SylWrap Pipe Repair Bandage
Water-activated wrap used to reinforce repairs by providing a rock-hard protective layer
Related Case Studies
Case Study: Rotted Wood Beam Repair in Renovation of Welsh Home
Case Study: Pipe Joints Sealed in Cast Iron Rainwater Stack Repair at London Office Block
Case Study: Seawater Storage Tank Floor Repair at Gas Processing Plant in Saudi Arabia
Case Study: Environment Agency Repair Crack in Underwater Wall Between River & Trout Farm
Case Study: Fence Spurs Suffering from Concrete Cancer Filler Repair Using Epoxy Putty
Case Study: Repair of Leaking 350mm Effluent Pipe Running out to Sea Underneath Salt Marshes
If you have an application you would like to enquire about, please get in touch
Call: +44 (0)1444 831 459
Email: sales@sylmasta.com